SPECIFICATIONS
Load Rating: 20 amps @ 120 volts
Power Requirement (no load): 10 watts
Surge Let-Through Voltage (6000-volt surge): 0 volts
UL 1449 Adjunct Classification Test Results: 1000 surges, 6000 volts, 3000 amps, B3 pulse; Measured suppressed voltage: 170 volts; no failures.
Federal Guidelines: Grade A, Class 1, Mode 1 (CID A-A-55818)
EMI/RFI Filter, Normal Mode (50-ohm load): 40 dB @ 100 kHz; 50 dB @ 300 kHz; 50 dB @ 3 MHz; 50 dB @ 30 MHz
EMI/RFI Filter, Common Mode (50-ohm load): 18 dB @ 300 kHz; 30 dB @ 1 MHz; 50 dB @ 5 MHz; 50 dB @ 20 MHz
Maximum Applied Surge Voltage: 6000 volts*
Maximum Applied Surge Current: Unlimited, due to current limiting*
Maximum Applied Surge Energy: Unlimited, due to current limiting*
Endurance (C62.41-1991 Category B3 pulses): 1 kV>500,000; 3 kV>10,000; 6 kV>1000
Dimensions: 3.5" H x 19.0" W x 10.5" D (8.9 x 48.3 x 26.7 cm)
Weight: 16 lbs (7.3 kg)
Temperature Range: 5º to 35º C
Humidity Range: 5% to 95% R.H., non-condensing
Agency Listings: ETL and cETL (UL 1449, 2nd edition; CSA C22.2 No.8-M1986, R2000)
*1.2 x 50 µs pulse, industry standard combination wave surge, as per IEEE C62.41
Specifications subject to change without notice. SurgeX is a division of Electronic Systems Protection, Inc.
This product, including its components and/or processes carried out thereby, are covered by one or more of the following: U.S. Pat. No. 4,870,534. 4,870,528. 6,728,089. 6,744,613. 7,068,487. Can. Pat. No. 1,333,191. 1,332,439. Other Patents Pending. |
FEATURES
- Magnetic shielding steel enclosure
- 9' grounded 3-wire #12 line cord
- 12 grounded AC receptacles in two switched banks of six on rear panel, 2 receptacles always on
- Front panel courtesy receptacle
- Advanced Series Mode surge protection
- Advanced Impedance Tolerant EMI/RFI filtering
- Two power switches, one for each bank of outputs
- Thermal circuit breaker overload protection
- Self-test circuit with visual indicator
- 10-year warranty
- Made in U.S.A.
TECHNICAL DESCRIPTION
The SX2120 shall be a two-rack-space unit in a magnetic shielding steel enclosure. It shall operate from 120 volts AC and have a 9-foot, grounded, 3-wire #12 line cord. There shall be 12 grounded AC receptacles in two banks of six on the back panel, each bank with master power switch, as well as two receptacles always on, and one front-panel courtesy receptacle. There shall be a self-test circuit with visual indicator. Overall dimensions shall be 3.5” H x 19” W x 10.5” D. Weight shall be 16 pounds.
The SX2120 shall have a load rating of 20 amps at 120 volts, a self-test circuit with visual indicator and provide EMI/RFI filtering. t shall meet Federal Grade A, Class 1, Mode 1 guidelines for powerline surge suppressors and withstand at least 1000 occurrences of surge pulse voltages up to 6000 volts.


|