SPECIFICATIONS
AC Input
Number of Phases: Single (2W + G)
Power Cord: 6-ft. grounded, 3 wire, #14 line cord
Input Voltage (Acceptable Input Voltage): 120VAC (0 - 160VAC)
Input Voltage Range (Normal mode): 90 - 150VAC
DC Start Capability: Yes, (defaults to 60Hz)
Power Requirements (no load): 35 watts (charging), 15 watts (charged)
AC Output (Normal Mode)
Load Rating: 15 Amps @ 120 volts
Load Power Factor: 0.6
Outlets: 6 outlets (15 Amp) all with Advanced Series Mode surge elimination, 2 outlets with battery back-up
Output Frequency: Same as Input
Short Circuit Protection: Re-settable circuit breaker and electronically limited
Overload Capability: 110% - 5 minutes ≥120% - immediate shutdown
Output Voltage Regulation: 120VAC: -12.5% to +8.4%
Waveform: Same as Input
Boost Mode Voltage (Buck mode voltage): Nominal +16% (Nominal -14%)
Line Mode Voltage Range: 105 - 130VAC
Efficiency: Normal mode > 90%
AC Output (Battery Mode)
Capacity: 1000VA/600W
Back-up Run Time: 4 minutes 600W full load, 10.4 minutes 300W half load
Output voltage: Nominal 120VAC
Waveform: Stepped sine wave (simulated sine wave)
Topology: Single boost/buck line interactive, simulated sine wave
Battery Mode Voltage Regulation: Nominal ± 6% until LBW
Transfer Time: 6-10 ms
Output Frequency & Regulation: 50/60Hz ± 0.5Hz (Unless synchronized to utility)
Short Circuit Protection: Active electronic (current limit)
Batteries
Battery Rating: (2) 12V/7AH
Replacement: Hot swappable
Recharge Time: 8 hours to 90% after full load discharge
Surge Protection Specifications
Surge Protection: Advanced Series Mode® surge elimination
Surge Energy Rating: 6,000 volts/3,000 amps
Let through Voltage (6,000 volt surge): 0 volts
UL 1449 Adjunct Classification Test Results: 1000 surges, 6000 volts, 3000 amps, B3 pulse; Measured suppressed voltage: 170 volts; no failures.
Federal Guidelines: Grade A, Class 1, Mode 1 (CID A-A-55818)
EMI/RFI Filter, Normal Mode (50-ohm load): 40 dB @ 100 kHz; 50 dB @ 300 kHz; 50 dB @ 3 MHz; 50 dB @ 30 MHz
EMI/RFI Filter, Common Mode (50-ohm load): 18 dB @ 300 kHz; 30 dB @ 1 MHz; 50 dB @ 5 MHz; 50 dB @ 20 MHz
Maximum Applied Surge Voltage: 6000 volts*
Maximum Applied Surge Current: Unlimited, due to current limiting*
Maximum Applied Surge Energy: Unlimited, due to current limiting*
Endurance (C62.41-1991 Category B3 pulses): 1kV>500,000; 3 kV>10,000; 6 kV>1000
General Specifications
Warranty: (USA and Canada only) 10-year limited warranty
Battery Warranty: 2 years
Monitoring Software: Includes SentryPlus software
Communications: USB
Rack Size: 2U
Unit Dimensions (H x W x D): 3.5” x 19.0” x 10.5”
Unit Weight (lbs.): 32.0 lbs.
Operating Temperature: 32°F to 104°F (up to 5,000 ft above sea level (0°C to +40°C (up to 1,500 meters above sea level)
Operating Elevation: 32°F to 95°F (5,001-10,000 ft above sea level (0°C to +35°C (1,501 to 3,000 meters above sea level)
Storage Temperature/Relative Humidity: 5°F to 113°F (-15°C to +45°C) / 0 - 95% non-condensing
Humidity Range: 5% to 95% R.H., non-condensing
* 1.2 x 50 μs pulse, industry standard combination wave surge, as per IEEE C62.41.
** Specifications subject to change without notice.
|
FEATURES
- 2U Rack Mount
- 1000 VA Battery Backup
- Advanced Series Mode® Surge Elimination
- Impedance Tolerant® EMI/RFI Filter
- Automatic Voltage Regulation
- Over/Under Voltage Protection
- SentryPlus™ Power Management and Diagnostic Software
- USB port
- Self-test Circuit and Visual Indicator
- Receptacles: 6 Surge Elimination, 2 UPS / 4 Non-UPS
- 10 Year Product Warranty
- 2 Year Battery Warranty
- A-1-1 Certified
- RoHS Compliant
- Made in U.S.A.
TECHNICAL DESCRIPTION
The SU-1000-Li is a 1000 VA line interactive uninterruptible power supply, surge eliminator, and power conditioner in a magnetically shielded steel enclosure. It operates from 120 volts AC and has a 6-foot, grounded, 3-wire #14 line cord. It has 4 grounded AC receptacles and two of these provide battery back up protection. Overall dimensions are 3.5” H x 19.0” W x 10.5” D. Weight is 32.0 pounds.
The SU-1000-Li has a load rating of 15 amps at 120 volts, a self-test circuit with visual indicator, and provides EMI/RFI filtering. It meets Federal Grade A, Class 1, Mode 1 guidelines for power line surge suppressors and withstands at least 1000 occurrences of surge pulse voltages, up to 6000 volts. SentryPlus™ auto shutdown and monitoring software is also included with SU-1000-Li hardware.
SentryPlus™ Power Management and Diagnostic Software
- Plan a schedule to shutdown, restart, test UPS and control receptacles
- Customize programmable actions
- Set up notifications of user-defined power related events via pager, e-mail, audible alarm, network broadcast and SNMP trap
- View Real-time UPS data meters (voltage, frequency, loading percentage)
- Analyze power history and event records via software data and graphs
- Configure Multi-computer shutdown/wakeup through TCP/IP network
- Access remote monitoring, control and configuration through TCP/IP network
- Monitor and network multiple UPSs at a glance in a LAN
- Communicate to UPS using Universal Serial Bus (USB)
|