SPECIFICATIONS
Load Rating: 8 amps @ 120 volts
Power Requirement (no load): 10 watts
UL 1449-2 Adjunct Classification Test Results: 1000 surges, 6000 volts, 3000 amps, C1 pulse, Measured suppressed voltage 290 volts, no failures
Federal Guidelines: Grade A, Class 1, Mode 1 (CID A-A-55818)
Clamping Voltage Onset: 172 volts nominal (2 volts above peak line voltage, auto-tracking)
Filter (bi-directional, wave tracking): With 50 ohm load: 3 dB @ 3 kHz; 38 dB @ 100 kHz; 50 dB @ 300 kHz
Maximum Applied Surge Pulse Joule Rating: Unlimited, due to current limiting (8 x 20 µs)
Maximum Applied Surge Pulse Voltage: 6000 volts (1.2 x 50 µs pulse), industry standard rating
Maximum Applied Surge Pulse Current:
100,000 amperes (8 x 20 µs)
Endurance: IEEE C62.41-1991 Category B3 (C1)
Pulses: 1 kv>500,000; 3 kv>10,000; 6 kv>1000
Dimensions: 3.0" H x 7.5" W x 4.0" D (7.6 x 19.0 x 10.2 cm)
Weight: 5.4lbs (2.54 kg)
Temperature Range: 5º to 35º C
Humidity Range: 5% to 95% R.H., non-condensing
Agency Listings: ETL and cETL (UL 1449, 2nd edition; CSA C22.2 No.8-M1986, R2000)
Specifications subject to change without notice. SurgeX is a division of New Frontier Electronics Inc.
This product, including its components and/or processes carried out thereby, are covered by one or more of the following: U.S. Pat. No. 4,870,534. 4,870,528. 6,728,089. 6,744,613. 7,068,487. Can. Pat. No. 1,333,191. 1,332,439. Other Patents Pending. |
FEATURES
- Magnetic shielding steel enclosure
- 6’ grounded 3-wire #14 line cord
- 6 grounded AC receptacles
- Series Mode surge protection
- Thermal circuit breaker overload protection
- Self-test circuit with visual indicator
- 10-year warranty
- Made in U.S.A.
TECHNICAL DESCRIPTION
The SA966 shall be a compact standalone unit in a magnetic shielding steel enclosure. It shall operate from 120 volts AC and have a 6-foot, grounded, 3-wire #14 line cord. There shall be 6 grounded AC receptacles. Overall dimensions shall be 3.0" H x 7.5" W x 4.0" D. Weight shall be 5.4 pounds.
The SA966 shall have a load rating of 8 amps @ 120 volts. It shall be listed to UL 1449-2 and meet 1996 Federal Grade A, Class 1, Mode 1 Guidelines for powerline surge suppressors. There shall be three limiter circuits: a series surge reactor current limiter, a cascaded auto-tracking dual-polarity voltage limiter, and a pulse inverter. The onset clamping voltage shall be 172 volts nominal, and the unit shall have an instant-reacting snubber to protect against fast-rising surges generated within the installation location. The surge suppressor shall have an unlimited Applied Surge Current rating (8 x 20 µs) and shall withstand at least 1000 occurrences of Surge Pulse Voltages up to 6000 volts.
|