SPECIFICATIONS
Load Rating: 8 amps @ 120 volts
Power Requirement (no load):10 watts
UL 1449-2 Adjunct Classification Test Results 1000 surges, 6000 volts, 3000 amps, C1 pulse, measured suppressed voltage 290 volts, no failures
Federal Guidelines: Grade A, Class 1, Mode 1 (CID A-A-55818)
EMI/RFI Filter, Normal Mode (50-ohm load): 40 dB @ 100 kHz; 50 dB @ 300 kHz; 50 dB @ 3 MHz; 50 dB @ 30 MHz
EMI/RFI Filter, Common Mode (50-ohm load): 18 dB @ 300 kHz; 30 dB @ 1 MHz; 50 dB @ 5 MHz; 50 dB @ 20 MHz
Maximum Applied Surge Pulse Joule Rating: Unlimited, due to current limiting (8 x 20 µs)
Maximum Applied Surge Pulse Voltage: 6000 volts (1.2 x 50 µs pulse), industry standard rating
Maximum Applied Surge Pulse Current: Unlimited, due to current limiting (8 x 20 µs)*
Endurance: IEEE C62.41-1991 Category B3 (C1)
Pulses: 1 kv>500,000; 3 kv>10,000; 6 kv>1000
Overvoltage Shutdown: 145 volts (resume at 135 volts)
Dimensions: 1.75" H x 5.31" W x 9.06" D
Weight: 3.4 lbs
Temperature Range: 5º to 35º C
Humidity Range: 5% to 95% R.H., non-condensing
Designed to meet UL 1449, 2nd edition; CSA C22.2 No.8-M1986, R2000
*1.2 x 50 µs pulse, industry standard combination wave surge, as per IEEE C62.41
Specifications subject to change without notice. SurgeX is a division of New Frontier Electronics Inc.
This product, including its components and/or processes carried out thereby, are covered by one or more of the following: U.S. Pat. No. 4,870,534. 4,870,528. 6,728,089. 6,744,613. 7,068,487. Can. Pat. No. 1,333,191. 1,332,439. Other Patents Pending. |
FEATURES
- Magnetic shielding steel enclosure
- 3’ grounded 3-wire #18 line cord (separate)
- 2 grounded AC receptacles
- Series Mode surge protection
- Auto-resetting Overvoltage shutdown
- Thermal circuit breaker overload protection
- Self-test circuit with visual indicator
- 10-year warranty
- Made in U.S.A.
TECHNICAL DESCRIPTION
The SA82 shall be a compact mountable unit in a magnetic shielding steel enclosure. It shall operate from 120 volts AC and include a separate 3-foot, grounded, 3-wire #18 line cord. There shall be 2 grounded AC receptacles. Overall dimensions shall be 1.75" H x 5.31" W x 9.06" D. Weight shall be 3.4 pounds.
The SA82 shall have a load rating of 8 amps @ 120 volts. It shall be listed to UL 1449-2 and certified to Federal Grade A, Class 1, Mode 1 Guidelines for powerline surge suppressors. The unit shall provide auto-resetting overvoltage shutdown. There shall be three limiter circuits: a series surge reactor current limiter, a cascaded auto-tracking dual-polarity voltage limiter, and a pulse inverter. The onset clamping voltage shall be 172 volts nominal, and the unit shall have an instant-reacting snubber to protect against fast-rising surges generated within the installation location. The surge suppressor shall have an unlimited Applied Surge Current rating (8 x 20 µs) and shall withstand at least 1000 occurrences of Surge Pulse Voltages up to 6000 volts.
|